8 general specifications, General specifications -17 – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 365
![background image](/manuals/360271/365/background.png)
14-17
IM 04L31A01-01E
Specifications
14
14.8 General Specifications
Construction
Mounting angle:
Up to 30° of backward tilt angle allowed, no tilt to the left or
right
Mounting panel thickness:
2 to 26 mm
Material:
Case: Steel plate
Bezel: Polycarbonate
Color:
Case: Pale cobalt blue (DIC16-102 or equivalent)
Bezel: Charcoal gray light (Munsell 10B3.6/0.3 or equivalent)
Front panel:
Water and dust-proof (based on IEC529-IP65, and NEMA
No.250 TYPE 4 (except external icing test)
External dimensions:
288(W) × 288(H) × 220(D) mm
Weight (approx.):
CX2010: 6.6 kg, CX2020: 7.0 kg, CX2210: 6.9 kg, CX2220: 7.2 kg,
CX2410: 7.1 kg, CX2420: 7.5 kg, CX2610: 7.4 kg, CX2620: 7.7 kg
I/O Specifications
Control Output
Current output:
Number of outputs: 2 outputs/2 loops
Output signal:
4 to 20 mADC or 0 to 20 mADC
Load resistance:
600 Ω or less
Output accuracy:
±0.1% of span (1 mA or more)
Temperature drift:
±200 ppm/° C (output section)
Voltage pulse output:
Number of outputs: 2 outputs/2 loops
Output signal:
ON voltage = 12 VDC
Load resistance:
600 Ω or more
Resolution:
0.1%
Relay contact output:
Number of outputs: 2 outputs/2 loops
Output signal:
NC, NO, COM
Contact rating:
250 VAC, 3 A or 30 VDC, 3 A (resistive load)
Contact Input
Number of inputs:
6 inputs/2 loops
Input signal:
Non-voltage contact or open collector (TTL or transistor)
Input condition:
ON voltage:
0.5 V or less (30 mADC)
Leakage current when turned OFF:
0.25 mA or less
Input format:
Photocoupler isolation (2 points common)
Contact output
Relay output:
2 outputs/2 loops
Relay contact rating:
250 VAC, 1 A or 30 VDC, 1 A (resistive load)
Transistor output:
4 outputs/2 loops
Transistor contact rating: 24 VDC, 50 mA
Analog Input Section
Control PV input:
Up to 10 inputs (isolated) (the number of inputs varies
depending on the model and control mode)
Period: 250, 500, 1000 ms
Measurement input:
10 or 20 inputs (DCV, TC, and ID are isolated)
Period: 1 s or 2 s