Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 250
7-4
IM 04L31A01-01E
• When set to [TC] (thermocouple input)
Range
Selectable Measurement Span Range
R
0.0 to 1760.0 °C
S
0.0 to 1760.0 °C
B
0.0 to 1820.0 °C
K
–200.0 to 1370.0 °C
E
–200.0 to 800.0 °C
J
–200.0 to 1100.0 °C
T
–200.0 to 400.0 °C
N
0.0 to 1300.0 °C
W
0.0 to 2315.0 °C
L
–200.0 to 900.0 °C
U
–200.0 to 400.0 °C
PLATI
0.0 to 1400.0 °C
PR
0.0 to 1900.0 °C
WRe
0.0 to 2400.0 °C
• When set to RTD (resistance temperature detector)
Range
Selectable Measurement Span Range
Pt100
–200.0 to 600.0 °C
JPt100
–200.0 to 550.0 °C
• When set to [DI] (ON/OFF input)
Range
Selectable Measurement Span Values
Level
0: Less than 2.4 V,
1: Greater than or equal to 2.4 V
Cont
0: Open, 1: Closed
• When set to [Delta] (difference computation)
Type
Range
Selectable Measurement Span Range
Voltage
20mV
–20.00 to 20.00 mV
60mV
–60.00 to 60.00 mV
200mV
–200.0 to 200.0 mV
2V
–2.000 to 2.000 V
6V
–6.000 to 6.000 V
20V
–20.00 to 20.00 V
50V
–50.00 to 50.00 V
TC
R
–1760.0 to 1760.0 °C
S
–1760.0 to 1760.0 °C
B
–1820.0 to 1820.0 °C
K
–1570.0 to 1570.0 °C
E
–1000.0 to 1000.0 °C
J
–1300.0 to 1300.0 °C
T
–600.0 to 600.0 °C
N
–1300.0 to 1300.0 °C
W
–2315.0 to 2315.0 °C
L
–1100.0 to 1100.0 °C
U
–600.0 to 600.0 °C
PLATI
–1400.0 to 1400.0 °C
PR
–1900.0 to 1900.0 °C
WRe
–2400.0 to 2400.0 °C
RTD
Pt100
–800.0 to 800.0 °C
JPt100
–750.0 to 750.0 °C
DI
Level
–1 to 1
Cont
–1 to 1
7.1 Settings Related to Measurement Inputs