3 wiring, Wiring -5, Arrangement of the input/output terminals – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 122
2-5
IM 04L31A01-01E
Installation and Wiring
3
2
1
4
5
6
7
8
9
10
11
12
13
14
2.3
Wiring
Arrangement of the Input/Output Terminals
If you specify a model with 6 internal control loops and 20 measurement channels
(CX2620) and option terminals, seven terminal blocks are arranged on the rear panel of
the CX2000 as shown in the following figure. The option terminal block, which can be /
A6 [measurement alarm (6 DOs)], /A6R [measurement alarm (8 DIs, 6 DOs)], /A4F
[measurement alarm (4 DOs, with FAIL/memory end output relay)], /A4FR [measurement
alarm (8 DIs, 4 DOs, with FAIL/memory end output relay)], /CST1 [control DIO expansion
(12 DIs, 12 DOs)], or /TPS4 [24 VDC transmitter output (4 loops)], is installed at the
lower left section. If several terminal blocks are not installed according to the
specification made at the time of purchase, protection covers are attached in place of the
corresponding terminal blocks.
VIDEO OUT(VGA)
L N
Analog control input
terminal block
(10 inputs)
Measurement input
terminal block
(CH1 to CH10)
Measurement input
terminal block
(CH11 to CH20)
Loop 1 and 2 control
output terminal block
Loop 3 and 4 control
output terminal block
Loop 5 and 6 control
output terminal block
Option terminal block
(Options /A6, /A6R,
/A4F, /A4FR, /CST1,
and /TPS4)
Note
•
The installation position of each terminal block is fixed and cannot be changed.
•
For a description on the connection of communication interfaces such as the serial or Ethernet
interface, see the
DAQSTATION CX1000/CX2000 Communication Interface User’s Manual)
.
Input/Output Assignments of the Analog Control Input Terminal Block
There are 10 input terminals. When PV/SP computation is OFF, the PV inputs (PV) and
RSP inputs (RSP) are assigned as shown in the following figure depending on the
number of loops used and the control mode. The following figure denotes the three
terminals (/b, +/A, -/B) of a single column using a single cell. In addition, of the 12
columns of terminals, the columns at each end that have no terminal screws because
they are not used are omitted.
LOOP1
2
1
PV
(RSP)
(RSP)
PV
PV1
PV2
LOOP2
LOOP5
LOOP6
2
1
PV
1
PV
1
PV
(RSP)
PV
PV1
PV2
LOOP3
2
1
PV
(RSP)
(RSP)
PV
PV1
PV2
LOOP4
2
1
PV
(RSP)
PV
PV1
PV2
• 6 loops
PV, PV1, PV2: PV input, (RSP): RSP input
(not used during program control), : unused terminal
During single-loop control
During cascade control
During loop control with
PV switching
[Control mode setting]
LOOP4
LOOP3
LOOP2
LOOP1
2
1
3
2
1
3
2
1
2
1
PV
PV
(RSP)
(RSP)
(RSP)
(RSP)
PV
PV
PV1
PV1
PV2
PV2
PV
PV
(RSP)
(RSP)
(RSP)
(RSP)
PV
PV
PV1
PV1
PV2
PV2
• 4 loops
PV, PV1, PV2: PV input, (RSP): RSP input
(not used during program control), : unused terminal
During single-loop control
During cascade control
During loop control with
PV switching
[Control mode setting]