Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 214
![background image](/manuals/360271/214/background.png)
5-5
IM 04L31A01-01E
Program Control Related Setup Operations
5
5.4
Program parameter setting > Pattern start setting
This section explains the procedures for setting the start SP and conditions for starting
the operation.
Procedure
Opening the Setting Display
Press the keys in the following sequence:
MENU key
(switch to the setting mode (control)) >
#7 soft key
(select [Program-
control parameters]) >
#1 soft key
(select [Program parameter setting]) >
#3 soft key
(select [Pattern start setting])
Setup Procedure
1. Use the
arrow keys
to move the cursor (blue) to the item box you wish to change.
A soft key menu is displayed at the bottom of the display.
2. Press the
soft key
corresponding to the value you wish to select.
The box for the item you changed turns yellow, and the cursor moves to the next item.
3. Repeat steps 1 and 2 to change the value of all the items you wish to change.
4. Press the
DISP/ENTER key
to confirm the changes.
The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item box.
Setup Items
Pattern start setting
• Pattern number
Displays the pattern number selected in the pattern initial settings.
• Start target setpoint
Set the start SP, a starting condition, in the range of “EU (0.0% to 100.0%)” (initial value
is 0%) of the measurement span. The values can be copied and pasted using soft keys.
Only the loops that are set as follows are displayed: [Control] > [#1 Control action,
Input setting] > [Control mode] to a mode other than [Off] and [Program control] to
[On] and [Setting mode (Control)] > [#7 Program control parameters] > [#1 Program
parameter setting] > [Pattern initial setting ] > [Action loop] to [On]. During cascade
control, even-numbered loops within the same terminal block are not displayed.
• Start code
Select the operation start condition from the following. However, only the possible
loop conditions are displayed.
Starting target setpoint start, PV1 to PV 6 ramp-prioritized PV start, time-prioritized
ramp start (not displayed for segment time ramp setting method)