3. Drive functions

3−37

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

3.2.3

Homing sequence and parametrisation

The drive references with respect to a stop (or the current
actual position).

Sequence (does not apply to referencing at the actual
position):

1. Reset the homing status to Homing not executed".

2. Search for the reference point (mechanical stop).

3. Wait for standstill for 500 ms. Afterwards, the pressurized

cylinder chamber must have a chamber pressure measurĆ
ing at least 2/3 of the set operating pressure.

4. Determine the axis zero point/cylinder zero point by

setting the corresponding offset to the reference point
(current position = 0 + project zero point offset).

5. After reaching the stop, the CMAX sets the status

SPOS.REF = 1. The end of homing is signalised afterwards
with SPOS.MC.

Overview of parameters involved (see also section 5.4.12)

Parameters involved

Description

PNU

Axis zero point offset

1130

Homing method (permissible: −18, −17, 35)

1131

Homing speed

1132

Start (FHPP)

CPOS.HOME = positive edge: Start homing

Acknowledgement
(FHPP)

SPOS.ACK = positive edge: Acknowledge Start
SPOS.MC = 1: Movement completed
SPOS.REF = 1: Drive referenced

Tab. 3/13: Parameters involved in homing