2. I/O data and sequence control

2−9

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Control byte 1 (CCON)

Bit

EN

Description

B0
ENABLE

Enable Drive

= 0: Disable drive (controller)
= 1: Enable drive (controller)

B1
STOP

Stop

= 0: Stop active (execute stop ramp + cancel positioning task). The

drive stops with a stop ramp. The job is aborted and the standstill
monitoring is deactivated.

= 1: Enable drive.

Not permissible in parametrising mode.

A warning is signaled in parametrising mode if logic 1 is set.

B2
BRAKE

Open

Brake

= 0: Activate brake (0 V at brake output)
= 1: Release brake (24 V at brake output)
Note: The allocation can be inverted by parametrisation (PNU 522:02).
If the enable and brake are activated, the CMAX executes force control
with a force setpoint of 0.

B3
RESET

Reset Fault

With a

rising edge, any registered fault signal is cleared and, if successĆ

ful, the fault status is exited.

B4
ć

ć

Reserved, must be set to 0.
A warning is signaled for logic 1.

B5
LOCK

Lock Software
access

Access to the service interface (via FCT):
= 1: FCT may only observe. Not possible to take over the device control

(FCT).

= 0: The FCT can take over the device control (in order to modify paraĆ

meters or to control inputs).

B6
OPM1

Select
Operating
Mode

Bit 7 6

Operation mode

0 0

Record select mode, see section 2.2.3

0 1

Direct operating mode see section 2 2 4

B7
OPM2

Mode

0 1

Direct operating mode, see section 2.2.4

1 0

Commissioning, see section 2.2.5

1 1

Parametrising, see section 2.2.6