2. I/O data and sequence control
2−23
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
2.2.5
I/O data in commissioning mode
I/O data: Commissioning
Data
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Output
data
CCON
CPOS
Function
Param. 1
Parameter 2
(e.g. current workpiece mass)
Input
data
SCON
SPOS
Function
Progress
Primary actual value
(actual position)
Assignment of the control and status bytes (commissioning
mode):
Assignment of the control bytes (commissioning mode)
CCON
Byte 1
B7
OPM2
B6
OPM1
B5
LOCK
B4
ć
B3
RESET
B2
BRAKE
B1
STOP
B0
ENABLE
y
Mode selection
Block softĆ
ware acĆ
cess
ć
Reset
fault
Release
brake
Stop
Enable
drive
CPOS
Byte 2
B7
ć
B6
CLEAR
B5
TEACH
B4
JOGN
B3
JOGP
B2
HOM
B1
START
B0
HALT
y
ć
ć
Teach
value
Jog negaĆ
tive
Jog posiĆ
tive
Start
homing
Start
positionĆ
ing task
ć
Function
Byte 3
The function number selects the starting commissioning operation in commissioning mode.
The value is interpreted as enumeration. The functions are executed with a rising edge at
CPOS.START.
Value
Function
Description
Param. 1
Param. 2
0
Reserved
Not permissible
ć
ć
1
Identification
Execute identification run
= 0
Workpiece mass
2
Movement test
Execute movement test
= 0
= 0
3 to 255 Reserved
Not permissible
ć
–
When reserved functions are executed, the CMAX signals a corresponding error.
Param. 1
Byte 4
When executing a commissioning operation: Reserved = 0
When teaching: Teach target, see section 3.2.7.
A zero (0=) must be transferred in setpoint value bytes which aren’t used.
Param. 2
Bytes
5 to 8
Only for Identification" commissioning operation: Current workpiece mass in the set system of
units (see section B.1).
A zero (0=) must be transferred in setpoint value bytes which aren’t used.