4. Faults and diagnostics

4−31

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

4.3

Diagnostic parameters

4.3.1

Latest diagnostic status

The CMAX offers various parameters for the current diagnosĆ
tic messages.

PNU

Brief description

220

Active fault messages bit−encoded

221

Active warning messages, bit−encoded

224

Currently indicated fault ’Exx’ on the display

225

Currently active fault level

226

Current warning to be indicated in the FCT

227

Error status, bit−encoded for FCT

Tab. 4/4: Diagnostic parameters

Parameter

Description

Bit−encoded messages
PNU 220
PNU 221

Each parameter is a bitfield consisting of three uint32 values and thus
contains 3x 32 bits = 96 bit memory capacity. Each of these bits in this
array represents an error number. If it is set, the corresponding fault
message is active.
Example:
PNU 220:01 = 0x00000001

Bit 0 set

E01 active

PNU 220:02 = 0x00000040

Bit 38 (32+ 6) set

E39 active

PNU 220:03 = 0x00030000

Bit 80 (32 + 32 + 16) set

E81 active

Bit 81 (32 + 32 + 17) set

E82 active

This representation is optimized for evaluation by a PLC, since this bit enĆ
coding can be used directly to activate an MMI.
PNU 220: contains current faults
PNU 221: contains current warnings

Message on the disĆ
play
PNU 224
PNU 226

The PNU 224 contains the fault number currently being shown on the disĆ
play. This makes synchronisation between the display in the FCT and the
CMAX possible. It is always the fault that occurred first that is displayed.
The PNU 226 contains the warning number the FCT is supposed to display.
The warning is not shown on the CMAX display.