4. Faults and diagnostics
4−31
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
4.3
Diagnostic parameters
4.3.1
Latest diagnostic status
The CMAX offers various parameters for the current diagnosĆ
tic messages.
PNU
Brief description
220
Active fault messages bit−encoded
221
Active warning messages, bit−encoded
224
Currently indicated fault ’Exx’ on the display
225
Currently active fault level
226
Current warning to be indicated in the FCT
227
Error status, bit−encoded for FCT
Tab. 4/4: Diagnostic parameters
Parameter
Description
Bit−encoded messages
PNU 220
PNU 221
Each parameter is a bitfield consisting of three uint32 values and thus
contains 3x 32 bits = 96 bit memory capacity. Each of these bits in this
array represents an error number. If it is set, the corresponding fault
message is active.
Example:
PNU 220:01 = 0x00000001
Bit 0 set
E01 active
PNU 220:02 = 0x00000040
Bit 38 (32+ 6) set
E39 active
PNU 220:03 = 0x00030000
Bit 80 (32 + 32 + 16) set
E81 active
Bit 81 (32 + 32 + 17) set
E82 active
This representation is optimized for evaluation by a PLC, since this bit enĆ
coding can be used directly to activate an MMI.
PNU 220: contains current faults
PNU 221: contains current warnings
Message on the disĆ
play
PNU 224
PNU 226
The PNU 224 contains the fault number currently being shown on the disĆ
play. This makes synchronisation between the display in the FCT and the
CMAX possible. It is always the fault that occurred first that is displayed.
The PNU 226 contains the warning number the FCT is supposed to display.
The warning is not shown on the CMAX display.