Festo Контроллер позиционирования CPX-CMAX User Manual

Page 114

background image

3. Drive functions

3−52

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Project zero point and software end position sequence

These values can only be taught in commissioning mode.
The PLC must notify the CMAX what is being taught in the set
parameter 1 (byte 4).

1. Set commissioning mode.

(OPM2 = 1 + OPM1 = 0).

2. The last commissioning operation (e.g. identification)

must have been ended. Teaching is not permissible while
a commissioning operation is active and will lead to a
fault.

3. Via jog mode, the drive is put into the desired position by

positioning or manually (by moving by hand in Drive
(controller) disabled" state).
Note: The software end positions may be passed during
jogging. Outside of the software end positions, the drive
only moves at creeping speed.

4. Enter the teach target in the PLC output data. The function

number (byte 3) is ignored.

I/O data: Commissioning, teach function

Data

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Output
data

CCON

CPOS

Function

Param. 1:
Teach
target

= 0

Input
data

SCON

SPOS

Function

Param. 1:
Teach
target

Primary actual value

Teach target (byte 4)

Value

Applies to
PNU

What’s taught is

3

500:00

Project zero point

4

501:01

Negative software end position

5

501:02

Positive software end position