beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 169

background image

4. Faults and diagnostics

4−33

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Structure of an entry in the diagnostic memory

Time stamp

Days in

operation

milliseconds of

the day

Event

Diagnostic code

Additional

information

determines meaning

determines meaning

PNU 222

PNU 202

PNU 200

PNU 201

PNU 203

int32

int32

int32

int32

int32,
(bit−encoded)

Number of days in
operation

Number of milliĆ
seconds of the day

Diagnostic event

Diagnostic number Additional inĆ

formation for FCT

Tab. 4/7: Structure of diagnostic memory entry

Parameter

Description

Time stamp
PNU 202
PNU 222

Time of the diagnostic event since the delivery status, reset device data or
firmware download in milliseconds.
Ĉ PNU 222 contains the number of days
Ĉ PNU 202 contains the number of milliseconds of the day
The time stamp is not a real−time clock: The time is read from the device
data (PNU 140) when the message occurs. The CMAX counts the period of
operation.
When switching off, the current time (refer to PNU 140:02) is saved, and
retrieved when switching on.

Diagnostic event
PNU 200

Type of diagnostic message.
Not only fault messages are entered into the diagnostic memory, but also
switch−on operations, resets or configuration events.
The interpretation of the diagnostic code and the additional information
depends on the type of these events.

Diagnostic number
PNU 201

The diagnostic number contains a detail on the diagnostic event. In the
event of faults and warnings this is the exact fault number, in the event of
configuration event it is the function performed etc.

Additional information
PNU 203

Detailed information on the fault. The evaluation is complex and therefore
suitable for a PLC program to a limited extent only. For description see
section 4.3.3.

Tab. 4/8: Parameters of the diagnostic memory