5. Parameter
5−55
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
Upper limit setpoint force
PNU
PNU: 512
Index: 1
Max index: 1
Class: Var
Data type: int32
Values
Unit: Force (index = 3)
Linear drive
Semi−rotary drive
Dimension
Default
Minimum
Maximum
Force control is not permissible with semi−
SI 1 N
0
0
100.000
p
rotary drives.
Imperial 1 lbf
0
0
22.481
Largest permitted setpoint value for a force control. A larger setpoint value leads to a fault or
warning.
If both the smallest (PNU 511) and the largest (PNU 512) permissible force setpoint value are set to
zero, the setpoint limits are ignored when executing a force task.
o
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
ý
After writing, controller recalculation is carried out.
Permitted speed during force control
PNU
PNU: 514
Index: 1
Max index: 1
Class: Var
Data type: int32
Values
Unit: Speed (index = 6)
Linear drive
Semi−rotary drive
Dimension
Default
Minimum
Maximum
Dimension Default
Minimum
Maximum
SI 0,001 m/s
200
10
500
1
°/s
200
10
500
Imperial 0.01 ft/s
65
3
164
1
°/s
200
10
500
Max. permitted speed after start of a force command. This parameter is used for monitoring, not to
limit the speed. If the actual speed exceeds the set value, a fault is indicated, the axis stops and the
force command is cancelled.
The speed limit value must be significantly larger than the speed limit of parameters 406 / 554,
otherwise monitoring will lead to an error when reaching the speed limit. The speed limit value
should preferably be used as a security when the speed limiting (406/554) was deactivated.
o
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
o
After writing, controller recalculation is carried out.