3. Drive functions

3−57

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

3.3.1

Start of a record

Setpoint record
number
Output data

Acknowledge Start
SPOS.ACK

Motion Complete
SPOS.MC

Actual record
number
Input data

N − 1

N

N + 1

1

0

1

0

1

0

1

0

Start
CPOS.START

N − 1

N

1

0

1

2

3

4

5

6

7

t

min

t

min:

at least 1 bus cycle waiting time. Recommendation: 1 PLC cycle.

Not required if consistent data transmission is used.

Fig. 3/10: Record start sequence

1 Set the required record number in the PLC’s output data.

Until the start, the CMAX continues to reply with the numĆ
ber of the record last processed.

SCON.FAULT must be 0 during the entire sequence.

2 If SPOS.ACK (Acknowledge Start) = 0, the PLC can initiate

execution of the record with a rising edge at CPOS.START.