beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 147

background image

4. Faults and diagnostics

4−11

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Fault group 1 ć execution error

CPX error group 101 (CPX−MMI: [Execution error] )

No.

Message

Cause/description

Error handling

Type

1)

10

Homing not carried out

Drive with incremental
measuring system is not
referenced.

·

Carry out homing.

Level: F1
Reset: R
Info: x

11

No homing provided

Homing task in the case
of absolute measuring
system.

·

Do not carry out homing. Level: F1

Reset: R
Info: x

13

Wrong direction of moveĆ
ment during movement
test

Cylinder and valve are inĆ
correctly tubed.

·

Check tubing connecĆ
tion, exchange on cylinĆ
der or valve, if necessary.

Level: F2
Reset: R
Info: x

14

Movement test not carĆ
ried out.

Positioning task without
valid movement test.

·

Run movement test (recĆ
ommended) or skip.

Level: F2
Reset: R
Info: x

15

Result of movement test
not clear

Drive jammed.

·

Check low friction of
drive and guide, check
pressure build−up with
trace, if necessary.

Level: F1
Reset: R
Info: x

Obstacles on travel path.

·

Check travel path and
software end positions.

Working pressure not
sufficient to move the
mass.

·

Set sufficient working
pressure and check conĆ
figuration of the mass.

Cylinder not correctly proĆ
jected.

·

Check size and correct if
necessary.

Valve defective.

·

Check pressure build−up
with trace, exchange
valve if necessary.

Faulty tubing connection.

·

Check tubing connecĆ
tion.

Valves installed between
valve and cylinder
(emergency stop) are
closed.

·

Open valves.

1)

Level: fault level, see section 4.2.3
Reset: behaviour upon reset, see section 4.2.4
Info:

ć = no info; x = additional info, see FCT or section 4.3.3