Diagnostic memory

The diagnostic memory and the diagnostic parameters are
described in detail in the sections 4.3 and 4.4.

Diagnostic event

PNU

PNU: 200

Index: 1 ... 100

Max index: 100

Class: Array

Data type: int32

Values

Without unit

Default: 0

Minimum: −

Maximum: −

Type of diagnostic message, see section 4.3.2.
Not only fault messages are entered into the diagnostic memory of the CMAX, but also switch−on
operations, resets or configuration events. The interpretation of the diagnostic code and the addiĆ
tional information depends on the type of these events.

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.

Diagnostic number

PNU

PNU: 201

Index: 1 ... 100

Max index: 100

Class: Array

Data type: int32

Values

Without unit

Default: 0

Minimum: −

Maximum: −

The diagnostic number contains a detail on the diagnostic event. In the event of faults and warnings
this is the exact fault number, in the event of configuration event it is the function performed etc.

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.