beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 267

background image

5. Parameter

5−79

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

Supply pressure

PNU

PNU: 1141

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Pressure (index = 4)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0,1 bar

60

30

100

0,1 bar

60

30

100

Imperial 1 psi

85

44

145

1 psi

85

44

145

Supply pressure applied to the valve.

o

The parameter value cannot be changed.

ý

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.

Basic massload without workpiece

PNU

PNU: 1142

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Mass (index = 5)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0.1 kg

50

5

20.000

1 kg cm

2

50

1

2.000

imperial 1 lb

10

1

4.409

0.1 lb in

2

200

2

6.834

Basic mass or existing mass for all positioning tasks.

Calculation of the moving mass:
1 Moving mass without workpiece (PNU 1142)
This is the mass of the loading device fixed to the
slide. This mass must always be moved by the drive
(minimal mass to be moved).
2 Current workpiece mass (PNU 605/410/...)
If the drive also has to move workpieces of different
weights, this variable share must be defined as workĆ
piece mass.

The CMAX calculates the sum of both mass data for every positioning process. The respective mass
is determined based on the specified variable workpiece mass (PNU 605 is the global default value).
However, it is also possible to specifiy the workpiece mass individually in each record (PNU 410), in
jog mode (PNU 536) and in direct mode (PNU 544 or 51).

o

The parameter value cannot be changed.

ý

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.