5. Parameter
5−86
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
Force control filter factor
PNU
PNU: 1162
Index: 1
Max index: 1
Class: Var
Data type: int32
Values
Unit: Amplification (index = 10)
Linear drive
Semi−rotary drive
1)
Dimension
Default
Minimum
Maximum
Dimension Default
Minimum
Maximum
SI 0,01
100
10
1.000
0,01
100
10
1.000
Imperial 0,01
100
10
1.000
0,01
100
10
1.000
The signal filter factor can be used to influence the signal noise of the pressure sensors. When inĆ
creasing the factor, the filter becomes faster and consequently the noise lounder. At the same time
phase shift decreases.
1)
Force control is not permissible with semi−rotary drives. However, the parameter is used for standĆ
still control and should not be modified.
o
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
ý
This parameter can be written by FCT without higher−order controller.
ý
After writing, controller recalculation is carried out.
Force control timeout
PNU
PNU: 1163
Index: 1
Max index: 1
Class: Var
Data type: int32
Values
Unit: Time (index = 9)
Linear drive
Semi−rotary drive
Dimension
Default
Minimum
Maximum
Force control is not permissible with semi−
d
SI 1 ms
2.000
0
100.000
p
rotary drives.
Imperial 1 ms
2.000
0
100.000
Time within which the actual force must reach the tolerance window after the force ramp has reached
the target value. This means the time starts when setpoint value generation has elapsed.
If the time is set to 0, no monitoring is carried out.
o
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
ý
After writing, controller recalculation is carried out.