beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 266

background image

5. Parameter

5−78

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

Homing speed

PNU

PNU: 1132

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Speed (index = 6)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0,001 m/s

50

10

200

1

°/s

50

10

200

Imperial 0.01 ft/s

15

3

66

1

°/s

50

10

200

Speed at which the drive searches for the stop during homing.

o

The parameter value cannot be changed.

ý

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.

Mounting angle

PNU

PNU: 1140

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Mounting angle (index = 12)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0,1

°

0

−900

900

0,1

°

0

−900

900

Imperial 0,1

°

0

−900

900

0,1

°

0

−900

900

Mounting angle for the drive
A specification of −90

° to −0.1° means that the sensor zero point is at the top and the drive moves

downward towards larger positions. With values from 0.1 to 90

° the sensor zero point is at the botĆ

tom and the drive moves to the top.

o

The parameter value cannot be changed.

ý

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.