4. Faults and diagnostics
4−27
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Fault group 6 ć error in valve
CPX error group 106 (CPX−MMI: [Error in valve] )
continued
No.
Message
Cause/description
Error handling
Type
1)
65
Operating voltage of the
valve outside of the tolĆ
erance range (under−
voltage)
The valve reports inĆ
sufficient operating voltĆ
age. Either the cable
between the CMAX and
the valve is faulty or the
valve.
·
Check the cables at
the axis string.
·
Check the valve, exĆ
change if necessary.
Level: F2
Reset: F
Info: x
66
Overload at digital valve
output
The valve reports an
overload on the digital
output.
·
Check and correct the
circuitry.
Level: F2
Reset: F
Info: x
67
Overload at 24V supply
output of valve
The valve reports an
overload on the voltage
output.
·
Check and correct the
circuitry.
Level: F2
Reset: F
Info: x
68
Preliminary warning
valve over−temperature
The valve reports a high
operating temperature.
(Ambient temperature
too high).
·
Provide sufficient
cooling.
Level: W
Reset: F
Info: x
1)
Level: fault level, see section 4.2.3; (can alternatively be parametrised as a warning or error)
Reset: behaviour upon reset, see section 4.2.4
Info:
ć = no info; x = additional info, see FCT or section 4.3.3