4. Faults and diagnostics

4−27

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Fault group 6 ć error in valve

CPX error group 106 (CPX−MMI: [Error in valve] )

continued

No.

Message

Cause/description

Error handling

Type

1)

65

Operating voltage of the
valve outside of the tolĆ
erance range (under−
voltage)

The valve reports inĆ
sufficient operating voltĆ
age. Either the cable
between the CMAX and
the valve is faulty or the
valve.

·

Check the cables at
the axis string.

·

Check the valve, exĆ
change if necessary.

Level: F2
Reset: F
Info: x

66

Overload at digital valve
output

The valve reports an
overload on the digital
output.

·

Check and correct the
circuitry.

Level: F2
Reset: F
Info: x

67

Overload at 24V supply
output of valve

The valve reports an
overload on the voltage
output.

·

Check and correct the
circuitry.

Level: F2
Reset: F
Info: x

68

Preliminary warning
valve over−temperature

The valve reports a high
operating temperature.
(Ambient temperature
too high).

·

Provide sufficient
cooling.

Level: W
Reset: F
Info: x

1)

Level: fault level, see section 4.2.3; (can alternatively be parametrised as a warning or error)
Reset: behaviour upon reset, see section 4.2.4
Info:

ć = no info; x = additional info, see FCT or section 4.3.3