A. Notes on commissioning and service

A−7

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Description of the statuses

PNU 1192:02 = 0

Searching for valve and measuring system.

This process takes max. 3 seconds.

PNU 1192:02 = 0

The CMAX has found no setpoint configuration. The system
of measurement units has not yet been defined.

The user must first define the system of measurement units.
As long as no system of measurement units has been confiĆ
gured, access to the axis parameters is restricted since the
CMAX does not know in what way the parameters need to be
scaled. You only have access to diagnostic data and to data
required by the FCT to define the system of measurement
units (measuring system type etc.).

The system of measurement units is defined with
PNU 1192:05.

The following data can be accessed in this status:

PNU:IND

Access

Description

1xx
2xx

Read/write

Device data: define device names,
version numbers
Diagnostic data: read current
fault

1190:01
1190:05
1190:11

Read

From hardware recognition:
cylinder type, sensor type, valve
type

1192:03

Read/write

carry out data reset

1192:05
1192:06

Read/write
Read

System of measurement units
System of measurement units
table

Tab. A/1: Access to parameters in status C00