Festo Контроллер позиционирования CPX-CMAX User Manual
Page 271
5. Parameter
5−83
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
Position control filter factor
PNU
PNU: 1152
Index: 1
Max index: 1
Class: Var
Data type: int32
Values
Unit: Amplification (index = 10)
Linear drive
Semi−rotary drive
Dimension
Default
Minimum
Maximum
Dimension Default
Minimum
Maximum
SI 0,01
100
10
1.000
0,01
100
10
1.000
Imperial 0,01
100
10
1.000
0,01
100
10
1.000
Position control filter factor, see section B.7
o
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
ý
This parameter can be written by FCT without higher−order controller.
ý
After writing, controller recalculation is carried out.
Position control timeout
PNU
PNU: 1153
Index: 1
Max index: 1
Class: Var
Data type: int32
Values
Unit: Time (index = 9)
Linear drive
Semi−rotary drive
Dimension
Default
Minimum
Maximum
Dimension Default
Minimum
Maximum
SI 1 ms
2.000
0
100.000
1 ms
2.000
0
100.000
Imperial 1 ms
2.000
0
100.000
1 ms
2.000
0
100.000
Time within which the actual position must reach the tolerance window after the position setpoint
has reached the target value. This means the time starts when the setpoint value generation has
elapsed.
If the time is set to 0, no monitoring is carried out.
The time is additionally used for monitoring the start behaviour. If with a positioning task the drive
has not moved by at least 11 mm within the parametrised time after the start signal, a fault is generĆ
ated (setoff timeout")
Note:
Deactivation of the positioning timeout parameter may cause a record not to be concluded with MC
and to remain active permanently, e.g.:
Ĉ if the drive comes to a halt before its setpoint position (due to an obstacle),
Ĉ if the drive does not reach its setpoint position (depends on specified tolerance).
o
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
ý
After writing, controller recalculation is carried out.