6. Parametrisation

6−4

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

6.1.1 Request identifiers, response identifiers and error numbers

Description

ReqID

Request

ResID (+)

with response

ResID (ć)

in the event of

Request

with response

in the event of
an error

No request

0

0

0

Read parameter value

6

5

7

Change parameter value

8

5

7

Tab. 6/4: Request identifiers and response identifiers

Rules:

ć

There are the data types integer, character (char) and
bitfield.

ć

Each parameter value is transmitted as a 32−bit value.

ć

A string is an array of characters that can only be transĆ
mitted individually via the cyclic channel. The value NUL
(=0x00) is interpreted as the string end. A PLC must alĆ
ways transmit the zero as the last character.

ć

Simple variables have no subindex.
The transmitted subindex can have the values 0 and 1.
The value 0 corresponds to not used". It is recommendĆ
able to set the subindex to 1 as if the parameter were an
array with a component. Values that are > 1 are rejected
with error 3.