Festo Контроллер позиционирования CPX-CMAX User Manual
Page 66
3. Drive functions
3−4
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Continuous mode
In the case of continuous setpoint specification, an external
position setpoint is tracked. The setpoint values can be speciĆ
fied by the PLC/via the fieldbus.
The continuous setpoint specification is only possible in diĆ
rect operating mode and mainly corresponds with the free
profile.
Properties:
ć
Speed, acceleration and deceleration are limited to values
specified by the user (no automatic limitation).
ć
It is possible to set the mass at the start of continuous
positioning mode.
General properties
The following generally applies for position control:
ć
Setpoint values are filtered (low−pass) to smoothen"
jump−like changes.
ć
Following error monitoring (signal, if following error is
greater than the monitoring window).
ć
Monitoring of software end positions (end position limitaĆ
tion and warning).