beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 241

background image

5. Parameter

5−53

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

Software end position

PNU

PNU: 501

Index: 1 ... 2

Max index: 2

Class: Var

Data type: int32

Values

Unit: Position (index = 1)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0.01 mm

0

0

1.000.000 0,1

°

0

0

100.000

Imperial 0.001 in

0

0

393.701

0,1

°

0

0

100.000

Permissible range for position setpoint values. Starting with a target position outside of the limit
setpoint values is not permissible and will lead to a fault or warning. If the software end positions are
passed in the running process, the system will issue a warning. The offset to the axis zero point (not
to the project zero point!) is specified. Specifying 0 for both software end positions deactivates the
software end positions.
Index 1:

Lower software end position

Index 2:

Upper software end position

The controller checks the software end positions for plausibility and generates a fault, if necessary.
Notes on calculating the software end positions and a sample calculation of the maximum values can
be found in section B.2.4.

o

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.

Stop deceleration

PNU

PNU: 507

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Acceleration (index = 7)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0,001 m/s

2

10.000

10

100.000

1

°/s

2

10.000

10

100.000

Imperial 0.01 ft/s

2

3.000

3

32.808

1

°/s

2

10.000

10

100.000

Deceleration in the event of stop or fault. The stop ramp is only applied if it is larger than the decelerĆ
ation of the current task.

o

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.