4. Faults and diagnostics
4−30
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Fault group 8 ć measuring system error
CPX error group 108 (CPX−MMI: [Encoder error] )
continued
No.
Message
Cause/description
Error handling
Type
1)
84
Reference position of the
measuring system lost
Although the controller
has set the status to
Referenced", the
measuring system/
sensor interface reĆ
ported Not referenced".
·
Reference again.
Level: F2
Reset: N
Info: x
85
Operating voltage of the
measuring system/senĆ
sor interface outside of
the tolerance range (unĆ
dervoltage)
Operating voltage of the
measuring system too
low.
·
Check the power
supply.
·
Check the cables at
the axis string.
Level: F2
Reset: F
Info: x
87
Defective measuring sysĆ
tem cable or measuring
system in the electrical
end−position (potentioĆ
meter)
Faulty measuring system
cable.
·
Check the power
supply.
·
Check the cables at
the axis string.
·
It may be necessary to
switch on/off.
·
Exchange measuring
system or sensor inĆ
terface if necessary.
Level: F2
Reset: N
Info: x
Measuring system in the
electrical end position
(only potentiometer)
·
Move the measuring
system (potentioĆ
meter) away from the
end position.
89
Faulty data contents in
the position measuring
system / sensor interface
The position measuring
system / sensor interĆ
face contains incorrect
or contradictory data.
·
Switch the power
supply off and then on
again.
When the error is sigĆ
naled again:
·
Replace the measurĆ
ing system/sensor inĆ
terface.
·
Check firmware of the
CMAX.
Level: F2
Reset: N
Info: x
1)
Level: fault level, see section 4.2.3; (can alternatively be parametrised as a warning or error)
Reset: behaviour upon reset, see section 4.2.4
Info:
ć = no info; x = additional info, see FCT or section 4.3.3