beautypg.com

Procedure – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 35

background image

2. I/O data and sequence control

2−7

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

2.2

Structure of the cyclical I/O data in the operating modes

Data

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Output
data

Bytes 1 and 2 (fixed)
are retained in every
operating mode
(except byte 2 for
parametrisation).
They contain control

Bytes 3 to 8 depend on the selected operating mode (direct mode,
record select) and transmit further control and status bytes (e.g.
CDIR, SDIR,...), as well as setpoint and actual values:
Ĉ Record number or setpoint position in the output data
Ĉ Feedback of actual position and record number in the input data
Ĉ Additional operating mode− and control mode−dependent setĆ

Input
data

They contain control
and status bytes
(e.g. CCON,
SCON, ...) for enabĆ
ling the CMAX and
setting the operatĆ
ing modes

Additional operating mode− and control mode−dependent setĆ
point and actual values

Procedure

First define the operating mode in the CCON control byte. See
sections 2.2.1 and 2.2.2.

This results in the assignment of the other control and status
bytes:

ć

Record select mode, see section 2.2.3.

ć

Direct operating mode, see section 2.2.4.

ć

Commissioning mode, see section 2.2.5

ć

Parametrising mode, see section 2.2.6.

Recommendation: During operation, set the control bit
CCON.LOCK. This way, the PLC can ensure that the proĆ
grammed sequence cannot be disturbed by access with
the FCT.
Evaluate the status bit SCON.FCT_MMI, and take the missing
control access into consideration in the program sequence of
the PLC.