4. Faults and diagnostics

4−12

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Fault group 1 ć execution error

CPX error group 101 (CPX−MMI: [Execution error] )

continued

No.

Message

Cause/description

Error handling

Type

1)

16

Dynamic identification
failed

Incorrect mass parameĆ
trised or transferred in
parameter 2.

2)

·

Check mass and data.

Level: F1
Reset: R
Info: x

Too much mechanical
play in the system.

·

Check system strucĆ
ture.

Constructional design
not stable enough.

·

Check system strucĆ
ture.

Tubes used are too long.

·

Move valve closer to
the drive.

Compressed air not suffiĆ
ciently stable.

·

Check compressed air
supply.

17

Identification was not yet
executed

The static identification
was not executed during
record start, direct operĆ
ating or homing.

·

Execute static
identification

Level: W
Reset: F
Info: x

18

Clamping unit is still actiĆ
vated, operation enable
not possible

Operation enable was
given (CCON.STOP = 1)
although the clamping
unit had not yet been reĆ
leased.

·

Remove operation enĆ
able.

·

Release clamping unit.

Level: W
Reset: F
Info: x

1)

Level: fault level, see section 4.2.3
Reset: behaviour upon reset, see section 4.2.4
Info:

ć = no info; x = additional info, see FCT or section 4.3.3

2)

Parameter 2: Byte 4 ... 8 in commissioning mode.