beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 149

background image

4. Faults and diagnostics

4−13

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Fault group 1 ć execution error

CPX error group 101 (CPX−MMI: [Execution error] )

continued

No.

Type

1)

Error handling

Cause/description

Message

19

Impermissible mode
change

Change between record
select operating mode
and direct operating
mode during active posiĆ
tioning task
(SPOS.MC=0).

·

Reversing only
after completed
positioning task
(SPOS.MC = 1)

Level: F1
Reset: R
Info: x

Change between record
select operating mode or
direct operating mode
and commissioning or
parametrisation during
active operation enable
(CCON.STOP = 1).

·

Shifting only in stop
status.
Set CCON.STOP = 0
and wait for
SCON.OPEN = 0 and
SPOS.MC = 1

1)

Level: fault level, see section 4.2.3
Reset: behaviour upon reset, see section 4.2.4
Info:

ć = no info; x = additional info, see FCT or section 4.3.3