Echelon LonMaker User Manual
Page 355
LonMaker Turbo Editions User’s Guide
339
The Recovery category contains the following options. The changes you make in the Recovery
options category are applied to the current network on all LonMaker computers.
Subsystem Recovery
Options
If you select either of the following subsystem recovery options in
the LonMaker drawing, you need to resynchronize your drawing
and select the Update Location Path and ID in Devices check
box in the Synchronize LonMaker Drawings dialog box in order
to update the devices with the current subsystem location data.
To resynchronize your drawing, open the LonMaker menu, point
to Synchronization, and click Resynchronize.
Set SCPT Location
Value to Subsystem
Path
Stores the subsystem path in the SCPTlocation configuration
property of an application device when it is created. Automatically
updates SCPTlocation when the application device is
commissioned. The SCPTlocation configuration property must
apply to the Node Object functional block if the device has a Node
Object functional block, or it must apply to the entire device if the
device does not have a Node Object functional block.
Automatically updates the SCPTlocation
configuration property
when the application device is moved or its subsystem is moved or
renamed (provided that the
Update all Devices when Subsystem
Name is Modified option is set to Yes)
, or you select the
Update
Location Path and ID in Devices check box in the Synchronize
LonMaker Drawing dialog.
This check box is cleared by default.
If an application device and its functional blocks span multiple
subsystems, the LonMaker tool will use the subsystem path in
which the application device shape is located.
If the LonMaker tool cannot locate the applicable SCPTlocation
configuration property in an application device, the subsystem path