Set the reference – Fluke Networks CertiFiber Pro Users Manual User Manual
Page 92

Versiv Cabling Certification Product Family
Technical Reference Handbook
70
Set the Reference
The reference procedure for twisted pair cable sets the baseline
for insertion loss, ACR-F, and DC resistance measurements.
Set the reference at these times:
When you want to use the tester with a different remote. You
can set the reference for eight different remotes.
When you attach Class F/F
A
link interface adapters, such as the
optional DSX-PLA011 TERA
™
adapters.
Every 30 days. This ensures maximum accuracy of test results.
To set the reference
1
Turn on the tester and the remote a minimum of 1 minute
before you set the reference.
Note
Set the reference only after the testers are at an
ambient temperature between 50 °F and 104 °F
(10 °C and 40 °C).
2
Connect the main and remote testers together as shown in
Figure 25.
3
If you attached Class F/F
A
link interface adapters, make sure
you select a Class F or F
A
test limit. See the documentation
supplied with the adapters.
4
On the home screen, tap TOOLS, then tap Set Reference.
5
On the SET REFERENCE screen tap TEST.