Step 1: Set the Reference in Far End Source Mode

1-1 Turn on the tester and source let them sit for a minimum of

5 minutes. Let them sit longer if they are above or below
ambient temperature, or if the instructions for the source
specify a longer time.

1-2 Make sure that the home screen shows the correct settings for

the job, and the test type is Far End Source.

To make sure that other settings are correct, tap the test
setup panel, make sure the correct test is selected on the
CHANGE TEST screen, then tap EDIT to see more settings.
Table 8 on page 172 describes the settings.

1-3 Clean and inspect the connectors on the tester, source, and test

reference cords.

1-4 On the home screen tap SET REF.

1-5 In the TEST MODE window, select Auto CertiFiber Pro or the

type of source you will use, then tap DONE.

1-6 On the SET REFERENCE screen, tap RUN WIZARD.

Notes

To only set the reference, and not measure the
loss of your test reference cord, tap SKIP WIZARD
on the SET REFERENCE screen.
Fluke Networks recommends that you measure
the loss of your test reference cord each time you
set the reference.

1-7 Make the connections to set the reference as shown on the

screen, then tap NEXT to see the completed connections.
Figure 89 also shows the completed connections.