Step 6: turn on the auto save function – Fluke Networks CertiFiber Pro Users Manual User Manual
Page 342

Versiv Cabling Certification Product Family
Technical Reference Handbook
320
Step 5: Give Names to the Ends of the Fiber for OTDR Tests
Names let you identify the location of the fiber ends when you do
tests with an OTDR module. For example, End 1 is in the
telecommunications closet and End 2 is in a work area.
5-1 On the home screen, if the test type panel does not show the
Auto OTDR test, tap the panel, tap the Auto OTDR test, then
tap USE SELECTED.
5-2. On the home screen, tap the Next ID panel, then on the
CHANGE ID screen, tap the End 1: panel. See Figure 126.
5-3. On the EDIT END NAME screen, tap the field for End 1, then
use the keyboard to enter a name for End 1.
5-4. Tap the field for End 2, use the keyboard to enter a name for
End 2, then tap DONE.
5-5. On the CHANGE ID screen, make sure that the End 1/End 2
control at the top of the screen shows the end where you will
do the test (End 1 for this tutorial).
Step 6: Turn on the Auto Save Function
When Auto Save is on, the tester automatically saves results with
the next available ID. If a test fails, you can do the test again for
the same ID if necessary, or do a test for the next ID.
6-1 On the CHANGE ID screen, make sure that the Auto Save
control shows On.
6-2. Tap DONE.