Fluke Networks CertiFiber Pro Users Manual User Manual

Page 288

background image

Versiv Cabling Certification Product Family
Technical Reference Handbook

266

6

Tap TEST or press , then save the result.

7

Clean and inspect the connector for End 2 of the link, then
connect the tester to End 2.

8

Press , then tap the Next ID panel.

9

Tap the End 1/End 2 control at the top of the screen to make it
show End 2, then tap DONE.

10 Tap TEST or press .

11 Save the result with the same ID you used for End 1.

How To Do Bi-directional Tests for All IDs in a Set

In this procedure, you test all the links from End 1, then test them
all again from End 2.

1

On the home screen, tap the Next ID panel.

2

If necessary, tap CHANGE CABLE IDs to select or make an ID
set.

3

On the CHANGE ID screen, turn on the Auto Save function
and set the End 1/End 2 control to End 1.

4

Enter names for the ends of the fiber (optional):

a. On the CHANGE ID screen, tap the panel that shows End 1:.

b. On the EDIT END NAME screen, tap the End 1 and End 2

panels to use the keyboard to enter names for each end. Tap
DONE to save the names.

5

Tap DONE on the CHANGE ID screen.

6

Clean and inspect the connector for End 1 of the link that has
the first ID in the set.

7

Connect the tester to End 1 of the link, then tap TEST or press

.

8

Clean and inspect the connector for End 1 of the link that has
the next ID in the set.