Step 4: give names to the ends of the fiber, Step 5: set up launch fiber compensation – Fluke Networks CertiFiber Pro Users Manual User Manual
Page 70

Versiv Cabling Certification Product Family
Technical Reference Handbook
48
Step 4: Give Names to the Ends of the Fiber
Names let you identify the locations of the fiber ends. For
example, End 1 is in the telecommunications closet and End 2 is in
a work area.
4-1 On the CHANGE ID screen, tap the End: panel.
4-2 On the EDIT END NAME screen, tap the End 1 box, then use
the keyboard to enter a name.
4-3 Tap the End 2 box, use the keyboard to enter a name, then tap
DONE.
4-4 On the CHANGE ID screen, make sure that End 1 and the
name you gave End 1 shows. If End 2 shows, tap the End 1/End
2 control in the upper-right corner of the screen to make End
1 show.
4-5 Tap DONE.
Step 5: Set Up Launch Fiber Compensation
For this tutorial, you will use launch and tail cords.
5-1 On the home screen, tap the TOOLS icon, then tap Set
Launch Compensation.
5-2 On the SET LAUNCH METHOD screen tap Launch + Tail.
5-3 Clean and inspect the OTDR port and the launch/tail cord
connectors.
5-4 Make the connections shown in Figure 16.
5-5 Tap SET.
5-6 When the SET LAUNCH COMP screen shows, select the event
that is the end of the launch cord and the start of the tail cord.
When you do Launch + Tail compensation, the end of the
launch cord and the start of the tail cord are the same event.
5-7 Tap SAVE.