Step 7: Add Results from a Loss/Length Test
Select the loss/length test to do next on fibers 1A and 1B.
7-1 On the home screen, tap the test setup panel.
7-2. On the CHANGE TEST screen (Figure 127), tap the Smart
Remote test, then tap USE SELECTED.
7-3. Attach CertiFiber Pro modules to the main and remote Versiv
units.
7-4. On the home screen, the Next ID panel shows the first two IDs,
1A and 1B, that do not contain loss/length results. To see how
the tester uses the IDs for the fibers connected to its INPUT
and OUTPUT ports, tap the panel (Figure 130 on page 331).
7-5. Clean and inspect the connectors on the tester, remote, and
test reference cords.
7-6. To set the reference for the fiber test and make sure your test
reference cords are good, tap SET REF, tap RUN WIZARD, then
do the steps given by the wizard.
Note
When you make connections to the fiber link,
make sure you connect fiber 1A to the main
tester’s INPUT port and fiber 1B to the main
tester’s OUTPUT port.
7-7. When you have completed the reference and TRC verification
procedures and connected the testers to the fiber link, tap
TEST or press .
When the test is completed and if it passed, the tester
automatically saves the results for the Smart Remote test with
the OTDR results in IDs 1A and 1B. Figure 131 on page 332
shows the RESULTS screen for the tests completed for this
project.