For dsx modules and twisted pair adapters – Fluke Networks CertiFiber Pro Users Manual User Manual

Page 26

background image

Versiv Cabling Certification Product Family
Technical Reference Handbook

4

For DSX Modules and Twisted Pair Adapters

Warning

To prevent possible fire, electric shock, or personal
injury:

Do not connect the tester to telephony inputs,
systems, or equipment, including ISDN inputs.

Doing so is a misapplication of this product, which
can cause damage to the tester and make a possible
shock hazard for the user.

Always turn on the tester before you connect it to a
link. Doing so activates the tester’s input protection

circuitry.

Caution

To prevent damage to the tester or cables under
test, to prevent data loss, and to make sure your
test results are as accurate as possible:

Do not connect the tester to an active network.
Doing so causes unreliable test results, can disrupt
network operations, and can cause damage to the
tester.

Connect to the adapters only plugs that are made
for Ethernet applications, such as RJ45, ARJ45, and
Cat 7 plugs. Other types of plugs, such as RJ11
(telephone) plugs, can cause permanent damage to
the jacks.

To make sure your test results are as accurate as
possible, do the reference procedure every 30 days.
See “About Link Interface Adapters” on page 67.

Do not operate portable transmitting devices, such
as walkie-talkies and cell phones, during a cable
test. Doing so can cause errors in test results.

For permanent link adapters, do not twist, pull on,
pinch, crush, or make kinks in the cables. See Figure
24 on page 69.