Nortel Networks 1000M User Manual
Page 66
66
Bracing against earthquakes
Wall studs
Maximum height of wall
4 X 16 Gauge
4.8 m (16 ft)
4 X 14 Gauge
5.1 m (17 ft)
6 X 18 Gauge
6.0 m (20 ft)
Table 19 "Maximum wall heights for stud sizes: 0.6 m (24 in.)
spacing" (page 66)
lists the maximum wall heights for different sizes
of wall studs with a 24-inch spacing
Table 19
Maximum wall heights for stud sizes: 0.6 m (24 in.) spacing
Wall studs
Maximum height of wall
Wood Studs
2 X 4 (DF #2)
3.0 m (10 ft)
2 X 6 (DF #2)
5.1 m (17 ft)
Metal Studs
2 1/2 X 20 Gauge
2.4 m (8 ft)
2 1/2 X 18 Gauge
2.7 m (9 ft)
2 1/2 X 14 Gauge
3.0 m (10 ft)
3 5/8 X 20 Gauge
3.3 m (11 ft)
3 5/8 X 18 Gauge
3.6 m (12 ft)
3 5/8 X 16 Gauge
3.9 m (13 ft)
3 5/8 X 14 Gauge
4.5 m (15 ft)
4 X 20 Gauge
3.6 m (12 ft)
4 X 18 Gauge
3.9 m (13 ft)
4 X 16 Gauge
4.2 m (14 ft)
4 X 14 Gauge
4.8 m (16 ft)
6 X 18 Gauge
5.4 m (18 ft)
3
Determine where to place the fasteners.
Refer to
Figure 21 "Plywood fastener locations for wood and metal
stud walls, 16 inch spacing" (page 68)
through
fastener locations for concrete and masonry walls" (page 70)
if you
Nortel Communication Server 1000
Communication Server 1000M and Meridian 1 Small System Installation and Commissioning
NN43011-310
01.04
Standard
Release 5.0
13 May 2008
Copyright © 2008, Nortel Networks
.