Procedure 15 installing the ac power supply – Nortel Networks 1000M User Manual
Page 140
![background image](/manuals/191775/140/background.png)
140
Installing the power supplies for the Cabinet system
— Voltage: Recommended 100 to 240 V
Maximum limits 90 and 250 V
Single phase
— Frequency: 50 or 60 Hz
— Power (I/P Max): 750VA
Refer to the commercial power requirements in the chapters on system and
site requirements in Communication Server 1000M and Meridian 1 Small
System Planning and Engineering (NN43011-220) for detailed information
about power requirements.
WARNING
Wait at least five minutes after power to the unit is switched off
before removing the unit from the cabinet. Make sure that the
power cord and battery backup connection (if equipped) are both
disconnected.
CAUTION
Service Interruption
The NTDK70 AC power supply cannot power up on battery alone.
If the NTDK70 is powered down while operating on DC reserve
power, then AC power is required to power up.
Procedure 14
Installing the AC power supply
Step
Action
1
Set the AC breaker on the front of the power supply to the OFF
position.
2
Make sure that the switches on the power supply are properly set.
See
Figure 60 "NTDK70 and NTDK72 power supply switch settings"
.
3
Insert the power supply into the first slot on the left of the card shelf
(refer to
Figure 59 "Power supply location, main and expansion
).
4
Lock it into place with the card tabs.
5
Attach the power line cord to the connector on the left side of the
power supply (see
Figure 61 "AC power cable connection" (page
) by feeding the cord up through the card guides.
Nortel Communication Server 1000
Communication Server 1000M and Meridian 1 Small System Installation and Commissioning
NN43011-310
01.04
Standard
Release 5.0
13 May 2008