Connecting the telephones

WARNING

If connecting to a message waiting line card, unseat the
card from its assigned slot before continuing with the next
step.

3

Connect two NTAK9204 cables (one from connector J1 and one
from connector J2) from the protection module to the cross-connect
terminal.

Terminate the cables as shown in

Figure 136 "NE-500/2500-type

telephone cross-connections" (page 326)

.

4

Cross-connect the J1 cable to the Tip and Ring connections coming
from the line card.

Refer to

"Preprogrammed data" (page 373)

for default DN

assignments.

5

Cross-connect the J2 cable to the off-premise telephone.

6

Install the regulatory label provided with the Off-Premise Protection
Module on the inside right-hand wall of the cabinet (near the Velcro
wriststrap fastener) or chassis.

7

Install the line card in its assigned position.

Now, you can activate the telephone, as described in

"Activating

telephones" (page 336)

.

—End—