Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual
Page 704

Patch AMP
Chapter 41
41-2
When AMP is modified using this utility, no cross-reference checking is
performed. This means that almost any value can be assigned to any
available parameter regardless of the consequences.
Patch AMP contains a limited number of the total available AMP
parameters and is not intended as a substitute for ODS. Its intended
purpose is to allow minor changes to be made to an already-existing AMP
that has previously been downloaded to the control from the ODS
workstation or some other peripheral device.
Assuming that the control is powered up and the highest access password
has been entered, use the following procedure to get to the
{PATCH AMP}
softkey:
1.
Press the
{SYSTEM SUPORT}
softkey.
(softkey level 1)
PRGRAM
MANAGE
OFFSET MACRO
PARAM
PRGRAM
CHECK
SYSTEM
SUPORT
FRONT
PANEL
ERROR
MESAGE
PASS-
WORD
SWITCH
LANG
2.
Press the
{AMP}
softkey.
(softkey level 2)
PRGRAM
PARAM
AMP
DEVICE
SETUP
MONI-
TOR
TIME
PARTS
3.
Press the
{PATCH AMP}
softkey. The control will prompt you for an
additional password to access the patch AMP utility.
(softkey level 3)
AXIS
PARAM
PATCH
AMP
UPDATE
BACKUP
UPLD/
DWNLD
BACKUP
AMP
Important: If the
{PATCH AMP}
softkey is not visible on this softkey level,
the currently active access level does not permit the use of this utility.
Return to softkey level 1, press the
{PASSWORD}
softkey, and enter the
highest level password (access level 0). This password is assigned using
the AMP parameters discussed in chapter 22 for the 1st - 6th character of
the password.
4.
The patch AMP password is the word LOCK. Type in LOCK using
the operator panel keyboard and press the
[TRANSMIT]
key. The
control will display the patch AMP utility screen.