beautypg.com

7 amplifier slot number – Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual

Page 240

background image

Servo Parameters

Chapter 7

7-94

Function

Use this parameter when your servo is connected to an Allen Bradley 1394

digital drive. This parameter selects the 1394 drive axis module to which

the servo is connected. Each 1394 drive in your I/O ring can have up to

four amplifier axis modules (slots). They number from left to right, the

left most (closest to system module) being slot 0, the right most (furthest

from system module) being slot 3.

Axis

Parameter

Number

Axis

Parameter

Number

(1)

[1161]

(7)

[7161]

(2)

[2161]

(8)

[8161]

(3)

[3161]

(9)

[9161]

(4)

[4161]

(10)

[10161]

(5)

[5161]

(11)

[11161]

(6)

[6161]

(12)

[12161]

Range

0 to 3

Notes

This parameter must be set independently for each axis.

You must also identify the ring address of the 1394 drive using the

parameter ID of Amplifier Rack.

7.4.7

Amplifier Slot Number