Acc/Dec Parameters

Chapter 10

10-4

Figure 10.1

Exponential Acc/Dec

Time constant defined by the parameters

MANUAL or PROGRAMMED DELAY CONSTANT

Time (seconds)

0

63% of commanded

change in speed

EXPONENTIAL

Deceleration

EXPONENTIAL

Acceleration

Commanded

Feedrate

Feedrate

Important: Rapid moves that are made for a lathe control type when

performing a compound turning routine do not use this parameter. Rapid

moves for compound turning routines always use exponential Acc/Dec

regardless of the setting of this parameter. Be aware that if you choose

linear Acc/Dec for this parameter, and if you are going to use compound

turning routines, you must still configure the axes to allow rapid moves in

exponential Acc/Dec. This requires that the setting of the parameter for

the Programmed Delay Constant must be valid with the feedrate chosen as

the rapid feedrate for each axis. If improperly configured, the control may

generate a SERVO AMPLIFIER FAULT error when a rapid move is

executed in a compound turning routine.

Linear or S--Curve Acc/Dec as Per G--Code -- Use this parameter to
select the type of acc/dec mode (Linear or S--Curve) you want to

perform. Activating G47 enables Linear Acc/Dec. Activating G47.1

enables S--Curve Acc/Dec. S--Curve Acc/Dec is only applicable to

positioning moves in Exact Stop mode.