Error description – Yaskawa MotionWorks IEC Toolboxes User Manual

Page 440

background image

PLCopen Toolbox: Function Blocks

MotionWorks IEC61131-3 Toolboxes: 2013-09-13

427

true.

B

CommandAborted

BOOL

Set high if motion is aborted by another motion
command or MC_Stop. This output is cleared with the
same behavior as the Done output.

V

ActualSize

LREAL

The actual indexed distance

V

LatchPosition

LREAL

The slave's position in the CamTable when the latch
occurred

V

LimitedCorrection

BOOL

Indicates that the MaxCorrection is limiting the required
correction.

V

MissedLatch

BOOL

Cumulative number of latches missed

B

Error

BOOL

Set high if error has occurred during the execution of
the function block. This output is cleared when 'Execute'
or 'Enable' goes low.

B

ErrorID

UINT

If Error is true, this output provides the Error ID. This
output is reset when 'Execute' or 'Enable' goes low.

Error Description

ErrorID

Meaning

0

No error

4369

The move could not be buffered because the axis motion queue is full. 16 moves is the
maximum which can be buffered.

4370

The move could not be started because motion is prohibited. The drive may not be enabled.
MC_Power.Enable_Positive or MC_Power.Enable_Negative might be low. Check
MC_Power.Status output. MC_Stop.Execute might be held high, preventing motion. If
MC_Stop has control of the axis, no other function block can override the "Stopping" state.
Other blocks that try to cause motion while MC_Stop has control of the axis will generate
this error. Also verify that the limit switches are not active by checking the Global Variables
for the axis. Also, a motion block may be attempting to abort an MC_TorqueControl move.

4378

The function block is not applicable for the external axis specified

4381

Motion aborted due to axis alarm. It is also possible that a software limit has been
exceeded.

4391

The function block can not be used with a virtual axis.

4396

Axis latch function already in use.

4402

The scan compensation delay parameter 1305 is only valid for external encoders.

4403

The High Speed Output functionality is only available on external encoders.

4406

Continuous Latch Mode not supported on external encoders or non-Sigma V servopacks.

4624

4625

Axis ID does not correspond to an axis configured on the system. Verify the value of
AxisNum matches a logical axis number in the configuration. Tip: Make sure AXIS_REF is
properly declared as a VAR or VAR_GLOBAL in all relevant POUs.

4630

Trigger or pattern reference is not valid