Grass Valley Maestro Master Control Installation v.2.4.0 User Manual

Page 320

background image

320

MAESTRO — Installation and Service Manual

Section 8 — Software Installation

6.

From this point there are two possibilities:

A popup will show that the Processor update was successful.

Repeat

Step

above if another Processor is present. Otherwise,

go to

Step

below.

An error message may indicate that the “physical JTAG chain is

broken.” If this message appears, the FPGAs/CPLDs on the Pro-
cessor cannot be updated. Stop the installation process and then
contact Technical Support.

Updating FPGAs/CPLDs on the Hardware Control Panels

Follow these steps to update the FPGAs/CPLDs on the Hardware Control
panels

1.

In the board Status section of the screen, select the hardware control
panel to update.

2.

Right-click on the FPGA field for this control panel. The FPGA/CPLD
update menu will then appear. See

Figure 218

Figure 218. Control Panel FPGA/CPLD Update Menu

This menu shows the names of all FPGAs/CPLDs on the control panel
and the version number of the gateware now running (“loaded”) in
each device. Certain FPGA-type components and all of the CPLD-type
components can be updated using this menu. If a newer (“current”)
version of gateware is available for those components, the menu will
indicate the new version number and display a check box.

3.

Check the “Select All” box.

4.

Select

Update

. You will be asked to confirm the update.