beautypg.com

Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 92

background image

92

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 3

Drive Port 0 Parameters

DR

IVE CFG

Sta

rt

F

ea

tur

es

351

SleepWake RefSel
Sleep Wake Reference Select
Selects the source of the input controlling the Sleep-Wake function.

Default:
Min/Max:

0 (Disabled)
0 / 159999

RW 32-bit

Integer

352

Sleep Level
Sleep Level
Defines the analog input level that will stop the drive.

Units:

Default:

Min/Max:

Volt, P351 = 0 (Disabled)
Volt or mA, P351 = not 0 (Port
Device Jumper Setting)
5.00 Volt (P351 = 0)
5.00 Volt / 0.00 mA (Port n Device
Jumper Setting)
0.00 / 10.00 Volt
0.00 / 20.00 mA

RW Real

353

Sleep Time
Sleep Time
Defines the amount of time at or below 352 [Sleep Level] before a Stop is issued.

Units:
Default:
Min/Max:

Secs
0.00
0.00 / 1000.00

RW Real

354

Wake Level
Wake Level
Defines the analog input level that will start the drive.

Units:

Default:

Min/Max:

Volt, P351 = 0 (Disabled)
Volt or mA, P351 = not 0 (Port n Device
Jumper Setting)
6.00 Volt (P351 = 0)
6.00 Volt / 12.00 mA (Port n Device Jumper
Setting)
0.00 / 10.00 Volt
0.00 / 20.00 mA

RW Real

355

Wake Time
Wake Time
Defines the amount of time at or above 354 [Wake Level] before a Start is issued.

Units:
Default:
Min/Max:

Secs
0.00
0.00 / 64800.00

RW Real

356

FlyingStart Mode
Flying Start Mode
Enables/disables the function which reconnects to a spinning motor at actual RPM
when a start command is issued. Functional in all motor control modes.
“Enhanced” (1) – This advanced mode performs the reconnect function quickly.
“Sweep” (2) – This frequency sweep mode is used with output sine filters.

Default:
Options:

0 = “Disabled”
0 = “Disabled”
1 = “Enhanced”
2 = “Sweep”

(1)

(1) Frames 1…7 only

RW 32-bit

Integer

357

FS Gain
Flying Start Gain
P356 [FlyingStart Mode] = 1 “Enhanced”: Proportional term used in the current
regulator which controls the reconnect function.
P356 [FlyingStart Mode] = 2 “Sweep”: Time required for the speed detection signal to
remain at the programmed level (P360). Units of 50 μs.

Default:
Min/Max:

1200.0
0.0 / 10000.0

RW Real

358

FS Ki
Flying Start Intergal Gain
P356 [FlyingStart Mode] = 1 “Enhanced”: Integral term used in the current regulator
which controls the reconnect function.
P356 [FlyingStart Mode] = 2 “Sweep”: Integral term used in the voltage recovery to the
normal V/Hz level.

Default:
Min/Max:

60.0
0.0 / 1000.0

RW Real

359

FS Speed Reg Ki
Flying Start Speed Regulator Integral Gain
P356 [FlyingStart Mode] = 1 “Enhanced”: Integral term used in the speed regulator
which controls the reconnect function.
P356 [FlyingStart Mode] = 2 “Sweep”: Time to sweep frequency in one direction. Units
of 10 μs.

Default:
Min/Max:

100.0
0.0 / 10000.0

RW Real

360

FS Speed Reg Kp
Flying Start Speed Regulator Proportional Gain
P356 [FlyingStart Mode] = 1 “Enhanced”: Proportional term used in the speed regulator
which controls the reconnect function.
P356 [FlyingStart Mode] = 2 “Sweep”: Programmed level for the speed detection signal.
The monitored signal needs to drop below this level to indicate motor speed.

Default:
Min/Max:

75.0
0.0 / 100000.0

RW Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype