Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 59
Rockwell Automation Publication 750-PM001J-EN-P - October 2014
59
Drive Port 0 Parameters
Chapter 3
M
O
TO
R C
O
N
TROL
Mt
r Ct
rl
O
pti
on
s
1659
IPM Tran Angle
IPM Transition Angle
Difference Threshold between High and Low angle control to allow transition.
Note: This parameter is not used by Frame 8 drives and larger.
Units:
Default:
Min/Max:
Cnts
100.0
5.0 / 500.0
RW Real
1660
IPM Stc OfsTst K
IPM Static Offset Test Constant
Reduction factor for Static Offset test pulses.
Note: This parameter is not used by Frame 8 drives and larger.
Default:
Min/Max:
1.00
0.10 / 9.00
RW Real
1661
IPM Lq Cmd BW
IPM Lq Command Bandwidth
IqFddk Filter Bandwidth (BW) used to select the Active Lq for the IPM control.
Note: This parameter is not used by Frame 8 drives and larger.
Units:
Default:
Min/Max:
R/S
10.0
1.0 / 999.9
RW Real
Fi
le
Grou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-W
ri
te
Da
ta
T
ype