Port 10 and Port 11 Parameters
Chapter 4
IN
VERTER C
O
MMON
Sta
tus
13
Alarm Status
Alarm Status
RO
16-bit
Integer
Indicates whether the inverter has an alarm condition. See P107 [I1 Alarm Status] to view which alarms currently exist for inverter 1. Refer to
information on fault and alarm codes.
Fi
le
Grou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-W
ri
te
Da
ta
T
ype
755 (8+)
Options
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
In
ve
rt
er 2
In
ve
rt
er 1
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = No Alarm
1 = Alarm
Fil
e
Gro
u
p
No.
Display Name
Full Name
Description
Values
Read-W
ri
te
Da
ta
T
yp
e
IN
VE
R
TE
R
C
O
MM
O
N
Meterin
g
18
Ground Current
Ground Current
Ground current of AC output to a motor. This value is calculated based on the total
output currents (U, V, and W phases of the drive). When the three phases are balanced,
the ground current is ideally close to zero.
Units:
Default:
Min/Max:
Amps
0.0
0.0 / 5000.0
RO
Real
755 (8+)
Fil
e
Gr
ou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-Write
Da
ta
T
yp
e
INVERTER C
O
MMON
Co
nf
ig
ur
at
io
n
20
Recfg Acknowledg
Reconfiguration Acknowledgement
Acknowledge drive re-configuration for N-1 operation or drive rating change. Set to 1
“Acknowledge” (1) – Clears fault F361 “N-1 See Manual” and fault F362 “Rerate See
Manual.”
Default:
Options:
0 = “Ready”
0 = “Ready”
1 = “Acknowledge”
RW 32-bit
Integer
755 (8+)
21
See
.
Fil
e
Gr
oup
No.
Display Name
Full Name
Description
Values
Re
ad
-Write
Da
ta
T
yp
e
INVERTER C
O
MMON
Te
st
po
in
ts
30
32
Testpoint Sel 1
Testpoint Sel 2
Testpoint Selection 1, 2
Selects a source for [Testpoint Val n]. Used by the factory, typically for diagnostic
purposes.
Default:
Min/Max:
0
0 / 65535
RW 32-bit
Integer
31
33
Testpoint Val 1
Testpoint Val 2
Testpoint Value 1, 2
Displays data selected by [Testpoint Sel n].
Default:
Min/Max:
0.000000
–/+220000000.000000
RO
Real
755 (8+)
755 (8+)
755 (8+)
755 (8+)