Drive Port 0 Parameters
Chapter 3
APPLIC
AT
IONS
Id Compe
n
sa
ti
on
1618
IdCompRegen 3 Iq
Id Compensation Regen 3 Iq
Sets Iq value (in p.u.) at which P1617 [Id Comp Regen 3] (in p.u.) is specified.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Cntrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
0.7500
0.0000 / 5.0000
RW Real
1619
Id Comp Regen 4
Id Compensation Regen 4
Sets Id compensation value (in p.u.) at Iq = P1620 [IdCompRegen 4 Iq] (in p.u.) for
regenerative operation. Id compensation = Id Comp Regen 3 + (Id Comp Regen 4 – Id
Comp Regen 3) x (IqCmd – IdCompRegen 3 Iq) x 1/(IdCompRegen 4 Iq – IdCompRegen 3
Iq) for IqCmd = between IdCompRegen 3 Iq and IdCompRegen 4 Iq.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Ctrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
0.0000
–/+1.0000
RW Real
1620
IdCompRegen 4 Iq
Id Compensation Regen 4 Iq
Sets Iq value (in p.u). at which P1619 [Id Comp Regen 4] (in p.u.) is specified.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Ctrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
1.0000
0.0000 / 5.0000
RW Real
1621
Id Comp Regen 5
Id Compensation Regen 5
Sets Id compensation value (in p.u.) at Iq = P1622 [IdCompRegen 5 Iq] (in p.u.) for
regenerative operation. Id compensation = Id Comp Regen 4 + (Id Comp Regen 5 – Id
Comp Regen 4) x (IqCmd – IdCompRegen 4 Iq) x 1/(IdCompRegen 5 Iq – IdCompRegen 4
Iq) for IqCmd = between IdCompRegen 4 Iq and IdCompRegen 5 Iq.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Ctrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
0.0000
–/+1.0000
RW Real
1622
IdCompRegen 5 Iq
Id Compensation Regen 5 Iq
Sets Iq value (in p.u.) at which P1621 [Id Comp Regen 5] (in p.u.) is specified.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Ctrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
1.2500
0.0000 / 5.0000
RW Real
1623
Id Comp Regen 6
Id Compensation Regen 6
Sets Id compensation value (in p.u.) at Iq = P1624 [IdCompRegen 6 Iq] (in p.u.) for
regenerative operation. Id compensation = Id Comp Regen 5 + (Id Comp Regen 6 – Id
Comp Regen 5) x (IqCmd - IdCompRegen 5 Iq) x 1/(IdCompRegen 6 Iq – IdCompRegen 5
Iq) for IqCmd = between IdCompRegen 5 Iq and IdCompRegen 6 Iq.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Ctrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
0.0000
–/+1.0000
RW Real
1624
IdCompRegen 6 Iq
Id Compensation Regen 6 Iq
Sets Iq value (in p.u.) at which P1623 [Id Comp Regen 6] (in p.u.) is specified.
This parameter is active only in motor control mode flux vector induction (P35 [Motor
Ctrl Mode] = 3 “Induction FV”).
Default:
Min/Max:
1.5000
0.0000 / 5.0000
RW Real
Fi
le
Grou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-W
ri
te
Da
ta
T
ype
755
755
755
755
755
755
755
1629
See
for parameter numbers 1629 and 1637…1645.
1630
See
for parameter numbers 1630…1636, 1646, and 1647.
1648
See
for parameter numbers 1648…1661