Chapter 6
Troubleshooting
xx417
Safety Cflct
Alarm 1
Either
P9 [FB0 Loss Cfg] or P39
[FB1 Loss Cfg]
Indicates that the Safety DIP switches are in an invalid position.
xx420
FB0FB1 Cflct
Alarm 2
Indicates that the combination of the feedback selection done with P6
[FB0 Device Sel] and P36 [FB1 Device Sel] is invalid, i.e. both feedbacks
have Sin-Cos-Signals (There is only place for one set of Sin-Cos-Signals
on the Terminal Blocks). The drive cannot be started until this
configuration conflict is resolved.
xx421
Initializing
Alarm 2
Indicates that the Universal Feedback State Machine is in the Initialize
State. This Type 2 alarm makes sure that the motor cannot be started
during this.
(1) xx indicates the port number. Refer to
Fault and Alarm Display Codes on page 312
for an explanation.
Event
No.
(1)
Fault/Alarm Text
Type
Fault
Action
Configuration Param
Auto
Reset
Description