Example 4: wet well operation – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 496

496
Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Appendix C
Using DeviceLogix
Example 4: Wet Well Operation
This example demonstrates how basic control logic can be used for simple
applications. It is assumed that the PowerFlex 755 has an I/O module installed in
Port 4.
Figure 91 - Wet Well
The application consists of the following discrete I/O:
Type
Name
Description
Inputs
Fault Reset pushbutton
Used to reset any faults or alarms
Critical High Level sensor
Indicates a critically high level. It is normally a backup to the High Level
sensor and is also used to detect if the High Level sensor is faulty. When
ON, the drive will operate at an even higher output frequency in case it
is due to a high inflow.
High Level sensor
Indicates the well is at a high level and it is time to start pumping
(normal operation). The drive operates at a ‘normal’ rate unless the
Critical High Level was reached.
Low Level sensor
When OFF, it is used to indicate that the well is empty (as long as the
High and Critical High Level sensors are also OFF). The drive stops
operating (end of pumping cycle).
Outputs
Sensor Fault pilot light
Indicates that there is a problem with either the High Level or Low Level
sensors
Too Much Time Alarm pilot
light
If the drive operates for more than the normal amount of time it takes to
empty the well, there may be increased inflow or perhaps the Low Level
sensor is stuck ON. An alarm indication is made and the drive continues
to operate.
Critical High Fault flashing
light / alarm horn
Indicates a critically high level that requires immediate attention.
Outflow
Inflow
Critical High Level Sensor
High Level Sensor
Low Level Sensor