Embedded ethernet/ip (port 13) parameters – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 234

background image

234

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 5

Embedded Feature and Option Module Parameters

Embedded EtherNet/IP (Port
13) Parameters

For complete information on the Embedded EtherNet/IP feature, refer to the
PowerFlex 755 Drive Embedded EtherNet/IP Adapter user manual, publication

750COM-UM001

.

Fi

le

Gro

u

p

No.

Display Name
Full Name
Description

Values

Read-W

ri

te

Da

ta

T

yp

e

Embedded

EtherNet/IP

1
Thru
16

DL From Net 01

DL From Net 16

Datalinks From Network 01…16
Sets the port number and parameter number to which the selected Datalinks should
connect. Each selected port/parameter will be written with data received from the
network. These are parameters written by the controller (outputs from the controller).
If setting the value manually, the parameter value = (10000 x port number) +
(destination parameter number). For example, suppose you want to use P1 [DL From
Net 01] to write to Parameter 1 of an optional encoder module plugged into drive Port 5.
The value for P1 [DL From Net 01] would be 50001 [(10000 x 5) + 1].

Default:
Min/Max:

0
0 / 159999

RW 32-bit

Integer

17
Thru
32

DL To Net 01

DL To Net 16

Datalinks To Network 01…16
Sets the port number and parameter number to which the selected Datalinks should
connect. Each selected port/parameter will be read and their values transmitted over
the network to the controller. These are parameters read by the controller (inputs to the
controller).
If setting the value manually, the parameter value = (10000 x port number) +
(origination parameter number). For example, suppose you want to use P17 [DL To Net
01] to read Parameter 01 of an optional I/O module plugged into drive Port 4. The value
for P17 [DL To Net 01] would be 40001 [(10000 x 4) + 1].

Default:
Min/Max:

0
0 / 159999

RW 32-bit

Integer

33

Port Number

Port number
Displays the drive port to which the embedded EtherNet/IP adapter is dedicated. This is
always Port 13.

Default:
Value:

13
13 / 15

RO

32-bit
Integer

34

DLs From Net Act

Datalinks From Network Actual
Displays the number of actual controller-to- drive Datalinks that the drive is using based
on the I/O connection opened by the controller.

Default:
Min/Max:

0
0 / 16

RO

32-bit
Integer

35

DLs To Net Act

Datalinks To Network Actual
Displays the number of actual drive-to- controller Datalinks that the controller is using
based on the I/O connection opened by the controller.

Default:
Min/Max:

0
0 / 16

RO

32-bit
Integer

36

BOOTP

BOOTP
Configures the adapter to use BOOTP so that you can set its IP address, subnet mask, and
gateway address with a BOOTP server. When this parameter is disabled, you must use
the adapter parameters to set these addressing functions. This parameter is only
functional when the IP address switches are set to 001…254 or 888. Power cycle or
reset is required for change to take affect.

Default:
Options:

1 = “Enabled”
0 = “Disabled”
1 = “Enabled”

RW 32-bit

Integer

37

Net Addr Src

Network Address Source
Displays the source from which the adapter node address, subnet mask, and gateway
are taken. This will be switches, Parameters 38…41 [IP Addr Cfg n], or BOOTP. It is
determined by the settings of the octet switches on the adapter. See

Establishing A

Connection With EtherNet/IP on page 19

for details.

Default:
Options:

0 = “Switches”
0 = “Switches”
1 = “Parameters”
2 = “BOOTP”

RO

32-bit
Integer

755

755

755

755

755

755

755

755

755